Thermal conductivityThermal conductivity, thermal resistance, and thermal transmittance are the 3 commonly used properties related to material or system thermal insulation performance. The 3 properties and their differences are explained below.
Thermal conductivity represents the ability of a material to conduct heat.
Thermal conductivity is also called K-value and its unit is W/(m'K). The smaller the thermal conductivity, the better the thermal insulation performance.
Listed in the table below are the typical thermal conductivity ranges of selected building material types.
Building material typeTypical thermal conductivity rangeInsulation material (e.g. polyurethane/polystyrene foam, mineral wool)0.02 ' 0.04 W/(m'K)Wood, plywood, and gypsum board0.1 ' 0.5 W/(m'K)Coating (e.g. paint), plastics, and rubber0.1 ' 0.5 W/(m'K)Glass1 W/(m'K)Concrete (light weight or heavy weight), brick, and tile0.5 ' 2.5 W/(m'K)Metal (e.g. stainless steel or aluminum)15 ' 200 W/(m'K)Thermal conductivity is typically for homogeneous materials. For inhomogeneous materials (e.g. concretes or composite panels), their average thermal conductivity is referred to as the apparent thermal conductivity.
Thermal resistance represents the ability of a material layer to resist heat transmission. Thermal resistance is calculated as:
Thermal resistance is also called R-value and its unit is (m2K)/W. The greater the thermal resistance, the better the thermal insulation performance.
Thermal resistance is always in terms of one or multiple material layers with fixed thicknesses:
Thermal transmittance represents the ability of a wall, roof or fenestration system to transmit heat. Thermal transmittance is calculated as:
Thermal transmittance is also called U-value and its unit is W/(m2K). The smaller the thermal transmittance, the better the thermal insulation performance.
Thermal transmittance is always in terms of a complete wall/roof/fenestration system and air-to-air thermal transmission.
OTM provides two online thermal transmittance (U-value) calculators:
The discussions above follow typical engineering practices. In the academic context, the practices could be different.
If we use double glazing unit (DGU) glasses as an example, the engineering practice is to use its thermal transmittance (U-value), instead of the other two, for performance evaluations, though in the academic context it is still correct to calculate the apparent thermal conductivity and thermal resistance of a DGU glass.
In most applications, the primary feature of a thermal insulation material is its ability to reduce heat exchange between a surface and the environment, or between one surface and another surface. This is known as having a low value for thermal conductivity. Generally, the lower a material's thermal conductivity, the greater its ability to insulate for a given material thickness and set of conditions.
If it is really that simple, then why are there so many different terms, such as K-value, U-value, R-value, and C-value? Here is an overview with relatively simple definitions.
K-value is simply shorthand for thermal conductivity. The ASTM Standard C168, on Terminology, defines the term as follows:
Thermal conductivity, n: the time rate of steady state heat flow through a unit area of a homogeneous material induced by a unit temperature gradient in a direction perpendicular to that unit area.
This definition is really not that complex. Let's take a closer look, phrase by phrase.
Time rate of heat flow can be compared to water flow rate, e.g., water flowing through a shower head at so many gallons per minute. It is the amount of energy, generally measured in the United States in Btus, flowing across a surface in a certain time period, usually measured in hours. Hence, time rate of heat flow is expressed in units of Btus per hour.
Steady state simply means that the conditions are steady, as water flowing out of a shower head at a constant rate.
Homogeneous material simply refers to one material, not two or three, that has a consistent composition throughout. In other words, there is only one type of insulation, as opposed to one layer of one type and a second layer of a second type. Also, for the purposes of this discussion, there are no weld pins or screws, or any structural metal passing through the insulation; and there are no gaps.
What about through a unit area? This refers to a standard cross-sectional area. For heat flow in the United States, a square foot is generally used as the unit area. So, we have units in Btus per hour, per square feet of area (to visualize, picture water flowing at some number of gallons per minute, hitting a 1 ft x 1 ft board).
Finally, there is the phrase by a unit temperature gradient. If two items have the same temperature and are brought together so they touch, no heat will flow from one to the other because they have the same temperature. To have heat flow by conduction from one object to another, where both are touching, there must be a temperature difference or gradient. As soon as there is a temperature gradient between two touching objects, heat will start to flow. If there is thermal insulation between those two objects, heat will flow at a lesser rate.
At this point, we have rate of heat flow per unit area, per degree temperature difference with units of Btus per hour, per square foot, per degree F.
Thermal conductivity is independent of material thickness. In theory, each slice of insulation is the same as its neighboring slice. The slices should be of some standard thickness. In the United States, units of inches are typically used for thickness of thermal insulation. So we need to think in terms of Btus of heat flow, for an inch of material thickness, per hour, per square foot of area, per degree F of temperature difference.
After picking apart the ASTM C168 definition for thermal conductivity, we have units of Btu-inch/hour per square foot per degree F. This is the same as the term K-value.
If you want to learn more, please visit our website wall glass wool wholesale.
C-value is simply shorthand for thermal conductance. For a type of thermal insulation, the C-value depends on the thickness of the material; K-value generally does not depend on thickness (there are a few exceptions not in the scope of this article). How does ASTM C168 define thermal conductance?
Conductance, thermal, n: the time rate of steady state heat flow through a unit area of a material or construction induced by a unit temperature difference between the body surfaces.
ASTM C168 then gives a simple equation and units. In the inch-pound units used in the United States, those units are Btus/hour per square foot per degree F of temperature difference.
The words are fairly similar to those in the definition for thermal conductivity. What is missing is the inch units in the numerator because the C-value for a 2-inch-thick insulation board is half the value as it is for the same material 1-inch-thick insulation board. The thicker the insulation, the lower its C-value.
Equation 1: C-value = K-value / thickness
Typically, this term is used to describe the labeled performance rating of building insulation one can buy in a lumber yard. It is used less frequently for mechanical insulation, but it is still a useful term to understand. Its official designation is thermal resistance. This is how ASTM C168 defines it:
Resistance, thermal, n: the quantity determined by the temperature difference, at steady state, between two defined surfaces of a material or construction that induces a unit heat flow through a unit area.
ASTM C168 then provides an equation, followed by typical units. In the inch-pound units, thermal resistance is measured in degrees F times square feet of area times hours of time per Btus of heat flow.
Most people know that for a given insulation material, the thicker it is, the greater the R-value. For example, for a particular type of insulation board, a 2-inch-thick board will have twice the R-value of the 1-inch-thick board.
Equation 2: R-value = 1 / C-value
If the C-value is 0.5, then the R-value is 2.0. One can calculate it from the equation for C-value in Equation 1 above:
Equation 3: R-value = thickness / K-value
Thus, if the thickness is 1 inch, and the K-value is 0.25, then the R-value is 1 divided by 0.25, or 4 (leaving off the units for brevity).
Finally, there is U-value, known officially as thermal transmittance. This is more of an engineering term used to designate the thermal performance of a system as opposed to a homogeneous material. The ASTM C168 definition is as follows:
Transmittance, thermal, n: the heat transmission in unit time through unit area of a material construction and the boundary air films, induced by unit temperature difference between the environments on each side.
There are a few new terms: the boundary air films and between the environments on each side. The previous definitions did not refer to environments.
The best way to illustrate thermal transmittance or U-value is through an example. Consider the wall of a typical insulated house with nominal 2 x 4 boards (which actually measure about 1-1/2 inches x 3-1/2 inches), spaced 16 inches on center, running vertically. One might see 3/8-inch-thick gypsum wall board on the inside of the wall, with a plastic film vapor barrier separating the gypsum wall board from the wood studs. Fiberglass batts may be filling the 3-1/2-inch-wide spaces between the 2 x 4 studs. On the outside of the studs, there might be 1/2-inch-thick polystyrene insulation boards covered with exterior wood sheathing. This example will ignore doors and windows, as well as the K-value and thickness of the plastic sheet used as the vapor barrier.
The calculation of the wall's U-value is sufficiently complex to be beyond the scope of this article, but the following values must be known or at least estimated for its thermal transmittance to be calculated: *
The lower the U-value, the lower the rate of heat flow for a given set of conditions. A well-insulated building wall system will have a much lower U-value, or thermal transmittance, than an uninsulated or poorly insulated system.
To determine a mechanical insulation system's U-value accurately, one must account for heat transfer through the homogeneous insulation as well as through any breaches and expansion gaps with a different insulation material. There is also the outside air film and occasionally an inside air film.
In reality, many non-homogenous portions are typically unaccounted for. The standard thermal conductivity test procedures typically treat the material as being homogeneous. In real applications, there are joints and sometimes cracks in rigid materials. These inconsistencies make the U-value greater than if the insulation behaved as a homogeneous material.
The concepts of K-value, C-value, R-value, and U-value can be summed up in the following rules:
These are the properties upon which users of thermal insulation depend for energy savings, process control, personnel protection, and condensation control.
* Values for all of the above can be found in the ASHRAE Handbook of Fundamentals, Chapter 25: 'Thermal and Water Vapor Transmission Data.' Chapters 23 through 26 of the same ASHRAE manual also discuss calculation of the wall's U-value.
Figure 1Comparison of Several Insulation Materials
Figure 2Relationship between R-value and K-value
Figure 3Heat transfer through a building envelope is really a function of the wall's or roof's U-value, not just the R-value of the thermal insulation.
Figure 4This figure, Plate #26 from the Midwest Insulation Contractors Association (MICA) National Commercial and Industrial Insulation Standards (), gives an idea of why an insulation system will not perform as well as one would assume using continuous, homogeneous insulation.