NM is permitted in Tray [Table 392.3(A)]

Contact us to discuss your requirements of non metallic cable tray. Our experienced sales team can help you identify the options that best suit your needs.


With ladder tray you install the Cables per 392.9(A) generally. Since all the conductors are less than #4/0 then 392.9(A)(2) & Table 392.9, Column 1 specifically. Assuming the cross sectional area of the conductors is correctly computed to be 12 sq in. A 24” tray permits 28 sq in.fill.


Note: In the “other thread,” Don pointed out that Chapter 9, Table 1, note (9) does not apply to cable trays. I agree, but I don’t know of any other way to determine the proper cross sectional area of the NM.


Their ampacity is determined by 392.11(A). If they are a random lay, the ampacity is determined by 392.11(A)(1); basically, Table 310.16 and no derating.

If they have a maintained spacing not less than one cable diameter, the ampacity is determined by 392.11(A)(3).


In any case, the ultimate ampacity is still limited to the applicable 60?C rating.

392-Cable Trays: Page 2 of 10 - Solar365

trays shall be permitted to be used as equipment grounding conductors where continuous maintenance and supervision ensure that qualified persons service the installed cable tray system and the cable tray complies with provisions of 392.7.

(D) Hazardous (Classified) Locations. Cable trays in haz- ardous (classified) locations shall contain only the cable types permitted in 501.10, 502.10, 503.10, 504.20, and

505.15.

(E) Nonmetallic Cable Tray.

In addition to the uses per mitted elsewhere in 392.3, nonmetallic cable tray shall be

The company is the world’s best plastic fermentation tanks supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.

permitted in corrosive areas and in areas requiring
voltage
isolation.

392.4 Uses Not Permitted. Cable tray systems shall not be used in hoistways or where subject to severe physical damage. Cable tray systems shall not be used in ducts, plenums, and other air-handling spaces, except as permitted in 300.22, to support wiring methods recognized for use in such spaces.

392.5 Construction Specifications.

(A) Strength and Rigidity. Cable trays shall have suitable strength and rigidity to provide adequate support for all contained wiring.

(B) Smooth Edges. Cable trays shall not have sharp edges, burrs, or projections that could damage the insulation or jackets of the wiring.

(C) Corrosion Protection. Cable tray systems shall be corrosion resistant. If made of ferrous material, the system shall be protected from corrosion as required by

300.6.

(D) Side Rails. Cable trays shall have side rails or equivalent structural members.

(E) Fittings.

Cable trays shall include fittings or other suit

able means for changes in direction and elevation of runs.

(F) Nonmetallic Cable Tray.

Nonmetallic cable trays shall be made of flame-retardant material.

392.6 Installation.

(A) Complete System.

Cable trays shall be installed as a complete system. Field bends or modifications shall be so made that the electrical continuity of the cable tray system and support for the cables is maintained. Cable tray systems shall be permitted to have mechanically discontinuous segments between cable tray runs or between cable tray runs and equipment. The system shall provide for the support of the cables in accordance with their corresponding articles.

Where cable trays support individual conductors and where the conductors pass from one cable tray to another, or from a cable tray to raceway(s) or from a cable tray to equipment where the conductors are terminated, the distance between cable trays or between the cable tray and the raceway(s) or the equipment shall not exceed 1.8 m (6 ft). The conductors shall be secured to the cable tray(s) at the transition, and they shall be protected, by guarding or by location, from physical damage.
A bonding jumper sized in accordance with 250.102 shall connect the two sections of cable tray, or the cable tray and the raceway or equipment. Bonding shall be in accordance with 250.96.

(B) Completed Before Installation. Each run of cable tray shall be completed before the installation of cables.

(C) Supports. Supports shall be provided to prevent stress on cables where they enter raceways or other enclosures from cable tray systems.

Cable trays shall be supported at intervals in accordance with the installation instructions.
(D) Covers. In portions of runs where additional protec tion is required,