A: Ventilation effectiveness of laboratory HVAC systems can be evaluated by the following tools. These are listed in the order of complexity and comprehensiveness of the results.
E3 Green Technology supply professional and honest service.
1. Bulk flow Analysis
This technique assumes “well-mixed” conditions in a lab space. Dilution equations either in a steady-state or in transient format can be employed to estimate the extent of dilution by computing an average well-mixed concentration of contaminants. A simple spreadsheet can be developed for this analysis or by running the NIST CONTAM model. This is a zero-dimensional analysis, and hence, cannot predict spatial and temporal variations of contaminant concentration and resulting exposure of occupants. This technique can be used for existing facilities as well as for new conceptual designs. This can be used for rough estimation of dilution.
2. Smoke Visualization
Airflow Visualization Tests are conducted by generating a visible plume of smoke or other aerosol to observe airflow patterns in the vicinity of the source. However, such visualization is subject to the tracer release location, tracer properties, release rate and techniques employed for release of the tracer/smoke. Though such technique can provide visualization of airflow movement in space, it cannot provide any qualitative information on the potential distribution of contaminants. Also, how the space is lit, and the perspective taken by the observer, can highly influence the results. This technique is useful only for the existing facilities.
3. Tracer Gas Analysis
Air tracer techniques can be employed for the existing facilities to challenge ventilation systems and evaluate their ability to dilute and remove aerosolized pathogens. Ventilation Effectiveness Tests that employ air tracer tests can be used to measure accumulation and decay of concentration at certain discrete points in a space under the prevailing operating conditions. Air Tracer Tests involve generation of gases and particulates to simulate contaminant emissions and sensors to detect the migration, accumulation and dilution of contaminants within the space. However, such information is limited to the number, locations and type of sensors utilized during the test. Data collected at a few points in space may only present a limited picture of an entire 3D distribution in a space. Once again, this technique can only be applied for existing facilities.
4. Computational Fluid Dynamics (CFD) Analysis
CFD analysis involves numerical solution of three-dimensional equations of air motion, heat transfer, mass transfer and similar transport process. CFD analysis can predict and help visualize the most comprehensive three-dimensional airflow patterns, flow path of airborne contaminants and resulting distribution of contaminant in a 3D space. If performed properly with adequate expertise, CFD analysis can be an effective design optimization tool both for the existing and new facilities. During the early design process, CFD analysis help identify issues related to contaminant hazard and test various mitigation strategies before construction. However, CFD analysis requires expert knowledge of the science of numerical simulation, fluid mechanics and transport processes with adequate computational hardware and robust software. Furthermore, it is often evaluating a static condition, the movement of people, the opening of doors and the addition of high plug loads and large equipment can significantly alter the airflow conditions within the lab. So, it is often used as a design tool to define the optimum placement of supply diffusers and exhaust vents but may not represent actual conditions at any given time in the lab (this is common for all of these techniques).
A basic exhaust system consists of an enclosure and/or drops exhausted through ductwork that runs to a fan on the building roof. The appropriate type of exhaust system will depend on the processes and materials used in your research. Several types of laboratory ventilation are described below.
Chemical fume hoods are exhausted enclosures in research laboratories that when properly used minimize exposure to hazardous gases, vapors, and dust that may be encountered in laboratory processes. Instructions on proper fume hood use are contained in your Department’s Chemical Hygiene Plan. Special purpose fume hoods include:
Exposure Control Devices (ECD) includes gas cabinets, drops for vacuum pumps, adjustable snorkels and certain equipment that requires connection to an exhaust system. EHS works with researchers and Facilities in the design and installation of ECDs.
The company is the world’s best Laboratory Ventilation Solutions supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.
Most biosafety cabinets (BSCs) on the campus are Class II A2. While this type of BSC is designed to provide personnel and environmental protection against biological materials it is not suitable for volatile chemical use. Check with your EHS Biosafety Safety Officer if questions arise as to the safe use of biosafety cabinets.
In some cases, a lab may not require a fume hood or ECDs. General exhaust ventilation not associated with specific equipment may then be required to maintain a minimum air change rate in the lab. Areas that contain compressed or liquefied gases may also require general exhaust.
Each fume hood is surveyed yearly by the EHS office. This survey includes a check of the airflow, physical integrity, and alarm functionality. Before using a fume hood check to be sure the survey sticker is up to date.
Airflows at high priority ECDs are also checked yearly, less critical ECDs are checked at a longer interval.
Yearly biosafety cabinet certification is required and is each lab’s responsibility.
If your fume hood monitor alarm sounds or you feel that the exhaust ventilation is not working correctly, you need to take immediate action. Shut off any experiments or processes in the hood and post a “DO NOT USE” sign. Both the EHS Office and Facilities department will respond as quickly as possible to any problems involving laboratory ventilation.
Submit a work order to Facilities, mark it “URGENT”, and cc: . An alternative method to report an urgent problem to Facilities is by calling FIXIT (253-) which is answered 24/7. If you have questions about whether your hood monitor is working correctly or general questions about the safe operation of your hood, please contact the EHS Office at 617-452-.
Because they move conditioned air out of the lab continuously, fume hoods are highly energy-intensive. An older fume hood in an MIT lab can use more than 3 times as much energy annually as a single-family home. The energy to filter, move, cool and/or heat air is typically one of the largest energy demands in most lab facilities.
Innovations in fume hood technology and design are reducing airflow through fume hoods while maintaining safety. In one type of new hood (variable air volume), as the sash is lowered, the air volume passing through the hood is reduced while maintaining a minimum velocity. This results in energy savings from not having to filter, move, cool and heat, the additional air.
So keep your sash as low as possible when working in your fume hood, and closed completely when you are away from the equipment. Help MIT save energy and the environment: “Shut The Sash” Stickers are available to remind researchers to lower the fume hood sashes. To request them please contact the EHS Office.
Safe and Sustainable Labs Service Team was recently involved in a project to help hibernate fume hoods in the Chemistry undergraduate teaching lab. Fifty-eight fume hoods can now be hibernated with the push of a few buttons. To learn more, check out this article published by the Chemistry Department!
Light, fluffy nanomaterials may be disturbed by airflow in fume hoods. EHS recommends enclosures that have been developed for sensitive balances to handle these types of nanomaterials. Vendors have tested the balance enclosures and they work well to contain nanoparticles. The airflow from these enclosures can be HEPA filtered. Contact EHS for more information about working safely with nanomaterials
If you want to learn more, please visit our website Chemistry Fume Hood.