Pipe hangers that are installed in direct contact with the surface of the pipe, such as a pipe clamp, should have insulation applied over the hanger as well as the pipe. Cold piping supported by direct contact hangers should be insulated, to the maximum extent possible, to prevent condensation on the pipe and pipe hangers. Hot piping supported by direct contact hangers should have the hanger insulated for personnel protection as appropriate for the operating temperature and exposure conditions.
Zhiang Product Page
Pipe saddles are commonly used on large diameter piping where the load is exceptionally heavy or when contraction-expansion movement is expected. Pipe saddles are welded to the pipe and are used in conjunction with roller supports or on beam supports. Where possible, pipe saddles should be sized to be flush with the insulation material. If rollers are used and suspended from above, hanger rods should be spaced to allow clearance for the insulation. Insulation may be inserted into the void between the pipe and saddle if desired.
It is desirable to avoid breaks in the insulation system. Ideal designs should avoid thermal "shorts" which could lead to hot spots on hot systems, and condensation and icing problems on cold systems.
To eliminate those conditions, insulated piping is often supported using clevis hangers, and rolled metal insulation protection shields or "cradles" on the outside of the insulation.
Several factors govern the pipe span and size of the cradle (length, rolled width and thickness).
Following are the formulae to make the necessary calculations:
Where:
l = maximum allowable span between supports in m or ft
S = maximum allowable pipe stress, in MPa or lb/in²
Z = section modulus of pipe, in cm³ or in³
W = uniform weight of pipe, contents, insulation, in kg/m or lb/ft
Where:
l2 = maximum allowable span between supports limited by pipe deflection
δ = maximum deflection at the center of the span, measured in mm or in.
w = uniform weight of pipe, contents, insulation, in kg/cm or lb/in.
E = modulus of elasticity of pipe, in MPa or lb/in²
I = area moment of inertia of pipe, in mm4 or in4
The span lengths are typically calculated from these equations to limit deflection (δ ) of a pipe insulated with FOAMGLAS® cellular glass to less than 3.8 mm (0.15 in.)
Cradle design is based on a maximum bearing capacity that is calculated by applying a safety factor (typically 5) to the compressive strength. For standard grade FOAMGLAS® ONE™ material (compressive strength of 620 kPa / 90 psi) this would give a maximum bearing value of 124 kPa (18 psi) which would translate to a maximum bearing value of 1.3 kg/cm², allowing up to 3.8 mm (0.15 in. ) deformation in the cradle area without adversely affecting the insulation
A 120° arc has been established as the effective bearing contact angle for insulation in clevis hangers. Use a 30° contact angle for rollers or point load applications – which include rollers, flat beams, legs of a channel welded together to form a truss, and structural tees. The insulation/pipe interface is the surface of greatest stress and the surface on which the 1.3 kg/cm² (20 lb/in²) limit applies. Cradles should cover the bottom 180° of insulation to facilitate installation and retention.
Not clearly defining the pipe support’s cradle dimensions can lead to several issues that could compromise the mechanical performance of the entire pipeline.
Should one or several insulated pipe supports settle considerably or fail, it will create geometrical changes in the steel pipeline which may result in significant stresses, particularly near nozzles, flanges and fittings.
Calculation methods to determine the cradle dimensions have been developed and enable the designer to choose the correct dimensions in relation to other factors, such as the distance between the cradle, the load, and the type of capping materials.
Penetrations, pipe hangers, supports and gaps/joints all represent significant design and application problems for hot work, as well as for cold work. In both cases, they can be potential paths for moisture entry as well as sources of air leakage via induced natural convection. This can eventually lead to issues with energy loss and the formation of corrosion. Corrosion at pipe supports is one of the most common causes of external piping corrosion failures in processing environments and can seriously endanger the structural integrity of the pipeline.
Finally, a common mistake is not using the correct insulation material for a particular support. Ensure that the insulation material is suitable for the demands of the system and code requirements. Only closed-cell insulation should be allowed in below-ambient conditions. Also evaluate the flame and smoke ratings, which will differ for some materials depending on the insulation thickness.
Choosing the wrong type of insulated pipe supports can lead to high operating costs, heat loss, corrosion under insulation (CUI), and a several other issues.
For insulated pipe supports and hangers, the choice of an insulating material such as FOAMGLAS® cellular glass, which has a high compressive strength, enables the designer to avoid direct short circuits or at least to reduce these instances substantially. The purpose of avoiding thermal short circuits is because they could result in substantial heat transfer and condensation in low temperature applications. This condensation could be detrimental since the water, due to gravity, will tend by to penetrate the hanger box.
The impermeable nature of FOAMGLAS® insulation helps to ensure that the mechanical performance is not affected by the influence of moisture in liquid or vapor form. This will mitigate risks associated with corrosion and help to maintain the integrity of the insulated pipe support over the lifetime of the installation.
From an economic point of view, FOAMGLAS® insulation will keep its thermal efficiency over time as it is not susceptible to cell aging or decreasing thermal performance due to moisture penetration. This will help to eliminate hot or cold spots and help ensure that the overall system can run economically and operating costs are kept at a minimum.
Are you interested in learning more about Insulated Pipe Holder? Contact us today to secure an expert consultation!
FOAMGLAS® insulation is most suited to use in “dead weight load” support applications where the pipe is resting in a band style hanger, or on a rolled plate cradle. It is not suited for use in guides, (spider or cryogenic service) where thermal forces (live loads) can be in a magnitude much greater than simple dead weight load.
Insulated pipe support inserts (sometimes referred to as ‘blocks’) fit around a pipe where the pipe clamps are positioned, to both insulate and provide load bearing support. The inserts prevent contact between the pipe and the clamp which can lead to heat loss and condensation. They also provide a vapour barrier against moisture which can protect pipes from corrosion.
Traditionally insulation blocks are used on chilled water applications to help ensure a continuous run of insulation, where a complete vapour barrier is key to system integrity. However, they are also now increasingly used for other HVAC services since the changes to BS : recognised the energy-saving benefits of using insulated pipe supports on above ambient services.
Whilst pipe supports only come into contact with a small area of a total service run, if they are not insulated effectively, these points can account for a significant proportion of heat loss from above ambient temperature systems. This can undermine other measures put in place to improve energy efficiency.
In days gone by, hardwood blocks were the only option available. But thanks to new technologies and new product developments, there are now a number of alternatives which offer significantly superior thermal performance than wood blocks.
The main types of insulation block currently available are:
Despite their poor insulation properties, susceptibility to condensation and lack of fire resistance, wood blocks are still on the market, although their usage has declined significantly. The British Standard for insulated pipe supports, BS:, was updated to give the view that “wooden pipe supports should not be used” given their poor insulation properties.
Phenolic block offers one of the best all round solutions currently available, and is often the preferred choice. They are cost-effective, versatile and extremely thermally efficient. Phenolic blocks offer high levels of thermal insulation, an effective vapour and condensation barrier and a fire resistance level which means they have very low combustibility.
Mineral wool blocks are fairly new to the market. Their main benefit is for high temperature systems as they are non-combustible. So they would offer a good solution for very high temperature environments like power plants, refineries and chemical plants. Their overall thermal performance is not as robust as phenolic so they can be an expensive solution for chilled water and low temperature systems where phenolic provides a more all-round, cost-effective option.
Calcium silicate is another high temperature solution for those more specialist environments where temperatures exceed 120°C. It also has a high compressive strength. Therefore, it is an option best placed for more specialist environments.
For a more detailed comparison of phenolic, wood and mineral wool blocks, you can read our blog on the topic.
Generally it is not recommended to use wood blocks any longer unless there is a specific reason to, because the alternatives offer much superior performance. Ultimately, the choice depends on several factors including:
As mentioned, phenolic pipe insulation is a great all-rounder for chilled and low temperature systems and mineral wool has advantages for high temperature situations.
There are two British Standards that are relevant for insulated pipe supports.
BS gives the recommendation that load bearing insulated pipe supports should be used on chilled water and low temperature installations. It also states that “wooden pipe supports should not be used” any longer because of their poor performance regarding insulation and vapour barrier which is essentially the primary function of the pipe support. This standard has paved the way for superior products to be used such as phenolic blocks and mineral wool to make constructions more thermally efficient on the drive to net zero.
Installing the correct thickness of insulation around building services is essential to ensure they perform as expected. BS gives minimum or indicative insulation thicknesses for different applications. This is an important consideration because the thermal performance of different insulation products varies. For example, phenolic insulated pipe supports offer higher thermal insulation levels than mineral wool blocks, so each type of product would require a different thickness to deliver the same level of insulation.
Walraven Phenblox® are UK-made phenolic load-bearing pipe supports for steel, copper and plastic pipes. They are manufactured from high density phenolic foam in accordance with BS EN :. Here are some of their main characteristics:
*This is the highest performance achievable for phenolic foam blocks and means very limited contribution to fire, little or no smoke emissions and no burning droplets. The European Phenolic Foam Association (EPFA) gives an overview of the properties of phenolic foam.
View our product page for Walraven Phenblox® where you can find all the technical information about our phenolic.
Alongside Walraven Phenblox® we can offer a variety of Walraven pipe clamps to secure the insulated pipe supports in place, including our standard 2S clamps, HD Heavy Duty clamps and split bands. We have load bearing data available for our Phenolic block/2S clip combination if required, for added peace of mind. Whichever type of clamp you choose, our handy phenolic and clamp selection chart helps you choose the right combination of block and clip.
As well as manufacturing phenolic insulation blocks, we also provide all of the individual components that, when used together, create the complete pipe support system. This includes parts such as:
Our Projects and Technical Support Team can provide advice and designs should you require assistance in selecting the right combination of products for your installation.
The company is the world’s best Heat Insulation Pipe Bracket supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.